Research

Effect of Transverse Compression on the Dielectric Breakdown of Power Cable with Ethylene Propylene Rubber Insulation

DOE

Source: doe_osti

Questions this answers

Sources

Source record

The underlying research record — supporting evidence for the object above.

Key Details

Posted Date
Source
doe_osti

Description

Understanding of the failure mechanisms of submarine dynamic power cables (SDPC) is critical for innovative design to meet the 2035 cost reduction target of U.S. DOE Floating Offshore Wind Shot. This is important because the current design suffers a significant failure rate in the field. This project explored a multiphysics approach and conducted systematic electro-thermo-mechanical (ETM) experimental study on the power cores extracted from a 15 kV power cable. The power cable had three cores of copper conductor and ethylene propylene rubber (EPR) insulation. An ETM testing system with transverse compression capability was developed. Mechanical loading induced dielectric breakdown. Increasing temperature from room temperature (RT, 22 degrees Celsius) to 90 degrees Celsius resulted in the 67% decrease in the failure mechanical load as defined by the dielectric breakdown. With the same temperature rise, the creep mechanical load was reduced by 70% at a given dielectric breakdown time. The post-test measurement revealed an impressive recovery of electrical resistance, although the dielectric breakdown occurred in the ETM test that would not be captured without the use of ETM testing.. Authors: Wang, Hong [ORNL] (ORCID:0000000201730545); Wolfe, Eric [ORNL]; Duckworth, Robert [ORNL] (ORCID:0000000277735553). DOE Contract: AC05-00OR22725

Frequently Asked Questions

What is this record?+
It is a publication associated with DOE — published findings, a technical standard, or a notice. It reports results or specifications. There is nothing here to apply for.

Where this record sits

What else do you want to know?

100M+ government records — search across all categories