Behavior of Single-Line-Ground Faults in Inverter-Based Resource Dominated Grids Explained

DOE

Source: doe_osti

Questions this answers

Sources

Source record

The underlying research record — supporting evidence for the object above.

Key Details

Posted Date
Source
doe_osti

Description

It has been observed by protection engineers that it is difficult for a protective relay to identify the faulted phase during a single-line-ground (SLG) fault in a power system with a high ingression of inverter-based resources (IBR) using currents (phase or sequence). Further studies using electromagnetic transient (EMT) simulation show that the initial operating conditions of the IBRs influence the response of phase currents during an SLG fault. In this letter, we conduct a quantitative analysis using sequence components. We find that the pre-fault condition determines the relative position of the current contributed by the grid versus that from the IBR, and further dictates which phase has the largest magnitude during an SLG condition. Finally, this finding is further verified by the EMT simulation results.. Authors: Miao, Zhixin [Univ. of South Florida, Tampa, FL (United States)] (ORCID:0000000156234074); Fan, Lingling [Univ. of South Florida, Tampa, FL (United States)] (ORCID:0000000246861602); Fischer, Normann [Schweitzer Engineering Laboratories (SEL), Pullman, WA (United States)]. DOE Contract: EE0011474. Subjects: electromagnetic transient simulation; fault analysis; inverter-based resource; single-line-ground faults

Frequently Asked Questions

What is this record?+
It is a publication associated with DOE — published findings, a technical standard, or a notice. It reports results or specifications. There is nothing here to apply for.

Where this record sits

What else do you want to know?

100M+ government records — search across all categories